Column 1Description of Development
|
Column 2Conditions and Limitations
|
CLASS 56(a) The construction, erection or placing within the curtilage of an industrial building of a structure for the purposes of housing a (fully enclosed) Combined Heat and Power system.
|
1. The gross floor area of the structure shall not exceed 500 square meters.2. No such structure shall exceed 10 metres in height, or 50 metres in length.3. No such structure shall be within:(a) 10 metres of any public road. (b) 200 metres of the nearest habitable house or residential building or school, hospital, church or building used for public assembly (other than the house or building of the person providing the structure), save with the consent in writing of the owner, and, as appropriate, the occupier or person in charge thereof.
|
|
4. No such structure within 100 metres of any public road shall exceed 8 metres in height.
|
|
5. No such structure shall have more than 2 flues, neither of which shall exceed 20 metres in height from ground level.
|
|
6. The diameter of any flue shall not exceed 1 metre.
|
|
7. Noise levels must not exceed 43db(A) during normal operation, as measured at the nearest party boundary.
|
|
8. Not more than one such structure shall be erected. 9. The structure shall be used for the purposes of housing a Combined Heat and Power unit only.
|
(b) The construction, erection, or placing within the curtilage of a business premises, or a light industrial building, of a structure for the purposes of housing a (fully enclosed) Combined Heat and Power system.
|
1. The gross floor area of the structure shall not exceed 300 square metres.2. No such structure shall exceed 8 metres in height, or 40 metres in length.3. No such structure shall be within:(a) 10 metres of any public road.(b) 200 metres of the nearest habitable house or residential building or school, hospital, church or building used for public assembly (other than the house or building of the person providing the structure), save with the consent in writing of the owner, and, as appropriate, the occupier or person in charge thereof.
|
|
4. No such structure shall have more than 2 flues, neither of which shall exceed 16 metres in height from ground level.
|
|
5. The diameter of any flue shall not exceed 1 metre.
|
|
6. Noise levels must not exceed 43db(A) during normal operation, as measured at the nearest party boundary.
|
|
7. Not more than one such structure shall be erected within the curtilage of such a premises or building.
|
|
8. The structure shall be used for the purposes of housing a Combined Heat and Power unit only.
|
(c) The construction, erection or placing within the curtilage of an industrial building or light industrial building, or business premises of a wind turbine.
|
1. The turbine shall not be erected on or attached to the premises or building or any other structure within the curtilage of the building or premises.2. The total height of the turbine shall not exceed 20 metres.3. The rotor diameter shall not exceed 8 metres.
|
|
4. The minimum clearance between the lower tip of the rotor and ground level shall not be less than 3 metres.
|
|
5. The supporting tower shall be a distance of not less than the total structure height (including the blade of the turbine at the highest point of its arc) plus:(a) 5 metres from any party boundary,(b) 5 metres from any non-electrical overhead cables,(c) 20 metres from any 38kV electricity distribution line,(d) 30 metres from the centreline of any electricity transmission line of 110kV or more.
|
|
6. The turbine shall not be located within 5 kilometres of the nearest airport or aerodrome, or any communication, navigation and surveillance facilities designated by the Irish Aviation Authority, save with the consent in writing of the Authority and compliance with any condition relating to the provision of aviation obstacle warning lighting.
|
|
7. Noise levels must not exceed 43db(A) during normal operation, as measured from the nearest party boundary.
|
|
8. Not more than one turbine shall be erected within the curtilage of the premises or building.
|
|
9. All turbine components shall have a matt, non-reflective finish and the blade shall be made of material that does not deflect telecommunication signals.
|
|
10. No sign, advertisement or object, not required for the functioning or safety of the turbine shall be attached to or exhibited on the wind turbine.
|
|
11. The turbine shall not be located within an Architectural Conservation Area.
|
(d) The installation or erection on or within the curtilage of an industrial building, or any ancillary buildings within the curtilage of an industrial building, of solar panels (thermal collector or photo-voltaic).
|
1. The distance between the plane of the wall or a pitched roof and the panel shall not exceed 1 metre.2. The distance between the plane of a flat roof and the panel shall not exceed 2 metres.3. The solar panel shall be a minimum of 50cm from the edge of the wall or roof on which it is mounted.
|
|
4. The total aperture area of any wall mounted panel, or free-standing solar array shall not exceed 50 square metres.
|
|
5. Any equipment associated with the panels, including water tanks, shall be located within the roof space of the building.
|
|
6. The height of a free-standing solar array shall not exceed 2 metres, at its highest point, above ground level.
|
|
7. No sign, advertisement or object, not required for the functioning or safety of the panel shall be attached to or exhibited on the panels.
|
(e) The installation or erection on a business premises or light industrial building, or any ancillary buildings within the curtilage of such premises or buildings, of solar thermal collector panels.
|
1. Such a solar panel may not be installed or erected on a wall of such a premises or building.2. The total aperture area of any such panel, taken together with any other such panel previously placed on or within the said curtilage, shall not exceed 50 square metres or 50% of the total roof area, whichever is the lesser.
|
|
3. The distance between the plane of a pitched roof and the panel shall not exceed:(a) 50cm in the case of a light industrial building.(b) 15cm in the case of a business premises.
|
|
4. The distance between the plane of a flat roof and the panel shall not exceed: (a) 2 metres in the case of a light industrial building.(b) 1 metre in the case of a business premises.
|
|
5. The solar panel shall be a minimum of 50cm from the edge of the roof on which it is mounted, or 2 metres in the case of a flat roof.
|
|
6. Any equipment associated with the panels, including water tanks, shall be located within the roof space of the building.
|
|
7. The total aperture area of any free-standing solar array shall not exceed 25 square metres.
|
|
8. The height of a free-standing solar array shall not exceed 2 metres, at its highest point, above ground level.
|
|
9. A free-standing solar array shall not be located forward of the front wall of the building or premises.
|
|
10. No sign, advertisement or object, not required for the functioning or safety of the panel shall be attached to or exhibited on the panels.
|
(f) The installation or erection on a business premises or light industrial building, or any ancillary buildings within the curtilage of such premises or building, of photo-voltaic solar panels.
|
1. The total aperture area of any such panels, taken together with any other such panel previously placed on or within the said curtilage, shall not exceed 50 square metres or 50% of the total roof area, whichever is the lesser.
|
|
2. The distance between the plane of the wall and the panel shall not exceed 15cm.
|
|
3. The distance between the plane of a pitched roof and the panel shall not exceed: (a) 50cm in the case of a light industrial building.(b) 15cm in the case of a business premises.
|
|
4. The distance between the plane of a flat roof and the panel shall not exceed:(a) 2 metres in the case of a light industrial building.(b) 1 metre in the case of a business premises.
|
|
5. The solar panel shall be a minimum of 50cm from the edge of the wall or pitched roof on which it is mounted, or 2 metres in the case of a flat roof.
|
|
6. The total aperture area of any wall mounted panel, or free-standing solar array shall not exceed 25 square metres.
|
|
7. Any equipment associated with the panels, including water tanks, shall be located within the roof space of the building.
|
|
8. The height of a free-standing solar array shall not exceed 2 metres, at its highest point, above ground level.
|
|
9. A free-standing solar array shall not be located forward of the front wall of the building or premises.
|
|
10. No sign, advertisement or object, not required for the functioning or safety of the turbine shall be attached to or exhibited on the panels.
|
(g) The installation on or within the curtilage of an industrial building, or any ancillary buildings within the curtilage of an industrial building, of a ground source heat pump system (horizontal and vertical) or air source heat pumps.
|
1. The level of the ground shall not be altered by more than 1 metre above or below the level of the adjoining ground.2. The total area of any air source heat pumps shall not exceed 15 square metres.3. The air source heat pump shall be a minimum of 50cm from the edge of the wall or roof on which it is mounted.
|
|
4. Noise levels must not exceed 43db(A) during normal operation, as measured from the nearest party boundary.
|
|
5. Distances from party boundaries and from the foundations of any structure or building shall be maintained in line with the Sustainable Energy Ireland Renewable Energy Information Office Procurement Guidelines on Heat Pump Systems for the time being in force.
|
(h) The installation on or within the curtilage of a business premises or light industrial building, or any ancillary buildings within the curtilage of such a premises or building, of a ground source heat pump system (horizontal and vertical) or air source heat pumps.
|
1. The level of the ground shall not be altered by more than 1 metre above or below the level of the adjoining ground.2. The total area of any air source heat pumps shall not exceed 10 square metres.3. No such structure shall be constructed, erected or placed forward of the front wall of the building.
|
|
4. The heat pump shall be a minimum of 50cm from the edge of the wall or roof on which it is mounted.
|
|
5. Noise levels must not exceed 43db(A) during normal operation, as measured from the nearest party boundary.
|
|
6. Distances from party boundaries and from the foundations of any structure or building shall be maintained in line with the Sustainable Energy Ireland Renewable Energy Information Office Procurement Guidelines on Heat Pump Systems for the time being in force.
|
(i) The provision as part of a heating system for an industrial building or light industrial building or business premises of a biomass boiler, including a boiler house, flues mounted on the boiler house, and over-ground fuel storage tank or structure.
|
1. The gross floor area of the boiler house shall not exceed 20 square metres.2. The capacity of such a fuel storage tank or structure shall not exceed 75 cubic metres.3. The height of a boiler house or such a fuel storage tank or structure shall not exceed 3 metres.
|
|
4. The height of a flue mounted on a biomass unit shall not exceed 16 metres, measured from ground level.
|
|
5. No more than 2 flues shall be erected.
|
|
6. Not more than one such structure shall be erected within the curtilage of the site.
|
|
7. The diameter of any flue shall not exceed 1 metre.
|
|
8. The boiler house shall not be located within:(a) 10 metres of any public road. (b) 100 metres of the nearest habitable house or residential building or school, hospital, church or building used for public assembly (other than the house or building of the person providing the structure), save with the consent in writing of the owner, and, as appropriate, the occupier or person in charge thereof.
|
|
9. Noise levels must not exceed 43db(A) during normal operation, as measured from the nearest party boundary.
|
|
10. The fuel shall not include products derived from animal wastes or from wood containing dangerous substances.
|
CLASS 57The extension of a school, where the school has not been previously extended, by the construction or erection of an extension to the side or rear of the school.
|
1. The floor area of any such extension shall not exceed:(a) 160 square metres, or (b) 40% of the gross floor area of the school, whichever is the lesser.
|
|
2. No such structure shall be above the ground floor.
|
|
3. Any extension shall be a distance of not less than 2 metres from any party boundary.
|
|
4. Such structure shall comply with the Department of Education and Science Primary and Post Primary Technical Guidance Documents for the time being in force.
|